A green wire and a clamp on a pipe don’t look like much. They’re part of what lets a breaker trip when something goes wrong.

Russ Motyko, CMI® November 2026 5 min read 1,097 words

A clamp hanging loose near a water heater in Lake Oswego. Another in a Mulino mechanical room, clamped to nothing. A ground rod sticking up out of a Portland yard with no wire attached to it. Gas pipe bonding clamps cranked down over painted pipe in Ridgefield, Vancouver, Tigard and La Center.

Grounding and bonding parts are small and easy to bump, cut or forget during other work. In Russ’s recent reports, about 20 of 269 houses had a grounding or bonding finding at the service, the water piping or the gas piping. These are the parts buyers can’t judge from a photo, and they’re tied to how the electrical system handles a fault.

What grounding and bonding do

They’re two different jobs that use similar-looking wire.

Grounding connects the electrical system to the earth. Ground rods driven into the soil, a buried metal water pipe, or steel in the foundation concrete do that. The earth connection helps with lightning and power surges and keeps the system’s voltage steady relative to the ground.

Bonding connects metal things together: the panel, the metal water pipes, the gas piping and other metal piping. If a live wire touches a bonded pipe, the fault current has a low-resistance path back to the panel, and the breaker trips. Without bonding, the pipe can sit energized with nothing tripping, waiting for someone to touch it and a faucet at the same time.

The main bonding jumper is where the two systems meet. At the main service panel (and only there), the neutral and the ground are tied together. In a subpanel they’re kept separate. A Gladstone basement subpanel had the neutral and ground bonded together, and the same panel used a painted deck screw as its grounding screw. Subpanels get their own post later; the short version is that the neutral-to-ground connection belongs at the main service.

Ground rods and the grounding electrode conductor

The heavy bare copper wire that runs from the panel or meter to a ground rod is the grounding electrode conductor. Russ looks for it at the service and follows it where it’s visible.

The National Electrical Code, adopted with amendments in both Oregon and Washington, generally calls for a single ground rod to be backed up by a second electrode, usually a second rod at least 6 feet away, unless the one rod is shown to meet a resistance limit. Many older Portland-area houses have one visible rod. Some have none visible at all, which may mean it’s buried, or that the house relies on the water pipe.

The failures Russ wrote up were physical. A Portland property had a ground rod with a clamp on it and no wire running to it. Another Portland rod stuck up above the soil where a mower or a shovel could hit it. In Gresham, the ground wire was damaged and left exposed to more damage.

The water pipe ground and the repipe problem

For decades, the metal water line coming into the house served as a grounding electrode, and the electrical code still treats buried metal water pipe as one (it has to be supplemented by another electrode). That works as long as the pipe is metal all the way into the ground.

Repiping breaks it. When the old galvanized or copper line is replaced with PEX or other plastic, the ground clamp often stays on a short piece of copper that no longer goes anywhere. In one Portland house, the service appeared to use the original metal water pipes as its grounding electrode, and the house had since been repiped. In a Vancouver house, a ground clamp that may have been on the old water line was connected to nothing. A Lake Oswego report found a bonding jumper disconnected and hanging loose near the water heater.

The water heater jumper is its own small item. A short wire with a clamp on each end that bridges the hot and cold pipes at the water heater keeps the metal piping on both sides bonded, because the water heater’s fittings and dielectric unions can break that path.

Gas piping and CSST

Metal gas piping gets bonded too, so a fault onto a gas pipe trips a breaker. The most common finding in this whole group was a gas bonding clamp installed over paint. The electrical code calls for paint and other nonconductive coatings to be removed where a grounding or bonding connection is made. A clamp over paint may not make solid contact. Russ found this in about 10 houses, from Ridgefield and Vancouver to Tigard and Gresham.

Rust on the gas piping and meters with no protection from cars are the other common findings there. The post on rust on gas pipes and unprotected gas meters covers them.

Missing bonds came up too. A Springfield house had no visible bonding jumper at the gas meter, and a Clackamas house had the gas bonding wire disconnected and hanging.

CSST is the yellow or black flexible gas tubing common in houses built or remodeled since the 1990s. Its manufacturers require it to be bonded directly to the electrical system, because lightning striking nearby can arc through thin tubing that isn’t bonded and puncture it. Russ notes CSST when he sees it and looks for the bonding clamp. When he can’t find one, the report recommends an electrician or gas fitter confirm it.

Real Inspection Photos

Grounding and Bonding From Russ's Inspections

Ground rods, clamps and bonding wires Russ has written up at Portland-area houses.

  • Electrical bonding clamp installed on painted gas piping at the gas meter
    A gas bonding clamp tightened over painted pipe. The clamp needs bare metal under it to make good contact.
  • Grounding clamp on old metal water pipe next to new plastic piping in a crawlspace
    The service appeared to use the old metal water pipe as its ground, and the house had since been repiped with plastic.
  • Bonding wire and clamp hanging loose on a wall near a water heater
    A bonding jumper and clamp disconnected and hanging loose near the water heater.
  • Ground rod with a clamp in the soil next to a building with no wire attached
    A ground rod with a clamp on it and no grounding electrode conductor connected.
  • Painted deck screw used as the grounding screw inside an electrical subpanel
    A painted deck screw used as the grounding screw in a subpanel, where a listed fastener belongs.

See a full sample report

What a home inspection can and can’t see

Russ looks at the visible grounding and bonding connections: the grounding electrode conductor at the panel and meter, any ground rods above grade, clamps on water pipes and at the water heater, bonding at the gas meter and gas piping, and the neutral and ground arrangement inside the panel when the cover is removed. He tests a representative number of outlets with a tester, which shows whether an outlet has a ground path. The posts on two-prong outlets and GFCI protection cover what those outlet results mean.

He doesn’t measure ground rod resistance, dig for buried rods or trace wiring inside walls. When a connection is missing, loose, on paint or connected to nothing, the report recommends a licensed electrician evaluate the grounding and bonding system. A house with a pool or hot tub has a separate set of bonding rules, covered in the post on pool bonding.

Inspector Checklist
Grounding and bonding clues you can check
0 of 5 items verified
  • Look near the electric meter or panel for a bare copper wire running into the ground
  • Look at the gas meter for a clamp and copper wire on the pipe, and whether it’s on painted pipe
  • If the house was repiped with plastic, look for an old ground clamp on a dead-end piece of copper
  • Look for a short jumper wire across the pipes at the water heater
  • Ask the sellers whether the plumbing or the electrical service was ever replaced, and if an electrician checked the grounding afterward
Key Takeaway

Grounding ties the system to the earth; bonding ties the metal pipes to the system so a fault trips a breaker. Clamps on painted pipe, loose or dead-end clamps after a repipe, and damaged ground wires were the findings in Russ’s reports. A home inspection sees the visible connections, and an electrician can test the rest.

Older panels add their own grounding questions, and the post on fuse boxes in older homes covers one of them. To set up an inspection, you can book online.

Common Questions

Grounding and Bonding FAQ

Grounding connects the electrical system to the earth, through ground rods or a buried water pipe, mainly to handle lightning and surges and keep voltage stable. Bonding connects metal parts together, like water pipes, gas pipes and the panel, so that if a live wire touches one of them, the fault current has a clear path back and the breaker trips.
The National Electrical Code generally calls for a single ground rod to be supplemented with a second electrode, often a second rod at least 6 feet away, unless the one rod is shown to meet a resistance limit. Older houses often have one rod, or none visible. A home inspection can see the rods that stick out of the ground, not ones that are buried, and can’t measure resistance.
Metal gas piping can become energized if a wire faults to it or an appliance fails. Bonding ties it to the electrical system so a fault trips a breaker. Yellow-jacketed CSST flexible gas tubing has its own bonding requirements from its manufacturers, because lightning can damage thin tubing that isn’t bonded.
Paint doesn’t conduct electricity well. The electrical code calls for nonconductive coatings to be removed where a grounding or bonding connection is made. A clamp tightened over paint may make poor contact or none at all. Russ found this in about 10 houses.
It can. Many older houses used the metal water line as a grounding electrode. When the metal pipe is replaced with plastic, the clamp may be left on a short piece of copper connected to nothing. Russ found that pattern in Portland and Vancouver houses and recommended an electrician evaluate the grounding.
Russ checks outlets with a tester, which shows whether a ground path is present at that outlet. He looks at the visible grounding and bonding connections at the panel, meter, water pipes and gas piping. He doesn’t measure ground rod resistance or dig up buried connections. A licensed electrician can test the grounding system.
Russ Motyko, Certified Master Inspector, Portland Oregon
Russ Motyko, CMI®
Certified Master Inspector®  |  OR #1898  |  WA #1856

Russ is Oregon City’s only Certified Master Inspector® and a licensed general contractor. He has completed more than 3,000 inspections across the Portland metro and SW Washington. Bilingual in English and Russian, a U.S. Army Reserve Noncommissioned Officer, and owner of Trusted Home Inspections. Learn more →